Parameters Description:
Select the gas type used within the refrigeration system.
Total range of transducer*
Glide characteristic (Offset to Evap Temperature)
Select between Absolute or Gauge pressure
Pressure difference between suction transducer and evaporator 1
Pressure difference between suction transducer and evaporator 2
Pressure difference between suction transducer and evaporator 3
Pressure difference between suction transducer and evaporator 4
Pressure difference between suction transducer and evaporator 5
Pressure difference between suction transducer and evaporator 6
Pressure difference between suction transducer and evaporator 7
Pressure difference between suction transducer and evaporator 8
Pressure difference between suction transducer and evaporator 9
Pressure difference between suction transducer and evaporator 10
Alarm generated, once transducer fault delay expires, if the transducer fails.
Delay before the HP alarm is generated.
If the pressure exceeds this value then a High Pressure alarm is generated once the alarm
delay expires.
If the pressure exceeds this value the valves on controllers connected to the ML Switch will
closed or be reduced to a predetermined percentage. A MOP alarm is also created. (See MOP)
When the pressure reduces below this value valves on controllers connected to the Switch will
recover to their normal operational
When the Switch comes out of MOP, the valves will come on at 1 minute intervals and turn
“this” number of valves on per minute.
Delay after the MOP value has been exceeded before the MOP actions and alarm occurs.
Sets humidity high level.
When the timer is in the off period the trims will be pulsed at this value. Note if the humidity
sensor fails the trim relays will be pulsed at this level.
Off – Pulses the controller trim relays at the Trim Off Level.
On - trim control feature will continuously pulse the controller trim relays dependant
on the measured humidity.
Re mote – Uses Data Manager GP Timer channel to determine when to control. See
GP Timer Setup
* Span and Offset allows for the full range of the transducer to be used by the ML Switch.
Span is the full range of the transducer
Offset is the value below zero.
E.g. Danfoss AKS 33 with range: -1 bar to 12 bar
Span would be 190 (13 bar)
Offset would be -15 (-1 bar)